Peak sun hours (PSH) is the number of hours for which an irradiance of exactly 1000 W/m² would deliver the same daily energy a site actually receives. It is an energy figure expressed as time, not a count of daylight hours. A location receiving 5 kWh/m² over a day has 5 peak sun hours, even if the sun is above the horizon for thirteen.
Why 1000 W/m²
Module nameplate power is measured under standard test conditions, one of which is 1000 W/m² irradiance. Dividing a site's daily insolation by that same reference produces a number you can multiply directly by array kilowatts. Numerically, PSH in hours equals daily insolation in kWh/m².
Daylight hours are a different quantity. At sunrise and sunset the sun sits at a shallow angle and its light travels a longer path through the atmosphere, so irradiance is far below the reference. A summer day with thirteen daylight hours may hold only six or seven peak sun hours; a winter day with ten may hold three.
Turning PSH into an energy estimate
Daily yield ≈ array power × PSH × performance factor
Array power in kW, PSH in hours, and a dimensionless performance factor. For a healthy grid-tied system that factor is typically 0.75-0.85; for an off-grid system where energy also passes through a battery it usually falls to 0.6-0.7.
- Temperature: the largest summer loss. Power falls by roughly 0.3-0.4% per °C above 25°C, and rooftop cell temperature easily reaches 60-70°C.
- Soiling: commonly 2-5%, higher in dusty regions without regular cleaning.
- DC and AC cable drop: 1-3% with correctly sized conductors.
- Inverter conversion: about 2-4%, and tracking quality is part of the same chain — see what MPPT does.
- Mismatch, connectors and light shading: 1-3%.
A 5 kW array at 5 PSH with a 0.8 factor averages roughly 20 kWh a day. That is an estimate, not a guarantee. Run your own load figures through the solar system sizing calculator for a first pass.
Seasonal and latitude variation
PSH moves with latitude, altitude, cloud cover and dust. The ranges below are indicative and site-dependent; two points in the same city can differ.
| Climate zone | Winter | Spring/autumn | Summer | Annual mean |
|---|---|---|---|---|
| Temperate continental, 35-45°N | 2.5-3.5 | 4.5-5.5 | 6-7 | 4.5-5 |
| Humid coastal | 2-3 | 3.5-4.5 | 5-6 | 3.5-4.5 |
| Arid inland plateau | 3-4 | 5-6 | 6.5-7.5 | 5-5.5 |
| Desert and Gulf coast | 3.5-4.5 | 5.5-6.5 | 6.5-7.5 | 5.5-6.5 |
The seasonal spread matters more than the annual mean: in many mid-latitude locations December PSH is less than half of June PSH. So an off-grid array is sized on the worst month, while a grid-tied array can be sized on the annual mean because the grid absorbs the swing.
Tilt and azimuth
- Tilt: for maximum annual energy, use a tilt close to site latitude. To favour winter output, add roughly 10-15° to that.
- Azimuth: reference is true south in the northern hemisphere, not compass south. Up to about 15° off costs little, 30° costs a few percent, and east or west facing typically costs more than 15% of annual yield.
- Row spacing: on flat roofs, space rows so the front row casts no shadow on the next at midday on the shortest day.
Module temperature coefficient matters as much as nameplate watts in hot climates — see the solar panel selection guide.
How PSH feeds a battery bank calculation
- Total the daily load in watt-hours.
- Array power = daily load ÷ (worst-month PSH × performance factor).
- Usable bank energy = daily load × days of autonomy.
- Nominal bank capacity = usable energy ÷ permitted depth of discharge.
- Amp-hours = nominal capacity ÷ bank voltage.
A 3 kWh daily load with two days of autonomy needs 6 kWh usable. On a lead-acid bank held to about 50% depth of discharge that means roughly 12 kWh nominal — near 250Ah at 48V. A LiFePO4 bank, which tolerates deeper discharge, reaches the same usable figure at lower nominal capacity; the reasoning is set out in depth of discharge explained.
Frequently asked questions
What does peak sun hours actually mean?
It is the number of hours during which an irradiance of 1000 W/m² would deliver the same daily energy the site really receives. Numerically it equals daily insolation in kWh/m². It is an energy index and has no direct relationship to how long the sun is visible.
What performance factor should I use?
For a standard grid-tied system 0.75-0.85 is reasonable, and for an off-grid system with battery storage roughly 0.6-0.7. Choose the more conservative end where the site is dusty or cleaning is infrequent.
Which month's PSH should size an off-grid array?
The worst month the system must cover, usually midwinter. Sizing on the annual mean produces surplus in summer and a deficit in winter, and the bank is then discharged deeply on a routine basis, which shortens its life.